The AQ1000TN2 thermostat is used to control the ambient air temperature or floor temperature in hydronic heating application. It communicates with and is powered by an AQ2000 series zoning module to provide zoning control.
| Description | Hydronic Communicating Thermostat |
| Application | Hydronic single-stage zoning heat |
| Thermostat Type | 2-wire Communicating Thermostat |
| Type of Control Provided: | Proportional Integral (PI) |
| Network Zoning | Yes |
| Network Bus | Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to AQ2000 series zoning modules. |
| Zones | Single or Multi-zone |
| Power Method | Powered (24 Vdc) by AQ zoning module |
| User Interface (Programming) | LCD Display |
| User Interface (System Configuration) | DIP Switches |
| LCD Icons Displayed (Mode) | Heat On |
| LCD Icons Displayed (Mode) | Comfort/Unoccupied |
| LCD Icons Displayed (Mode) | Keypad Lock |
| LCD Icons Displayed (Mode) | Set point |
| LCD Icons Displayed (Mode) | Vacation Mode |
| Color | Premier White® |
| Mounting | Vertical Mount |
| Temperature Control Mode Selections | "A" for Ambient Air, "F" for Floor, "AF" for Ambient & Floor. |
| Temperatures Displayed: | Indoor, Set Point, Outdoor |
| Setting Temperature Range (C) | 5 C to 38 C |
| Setting Temperature Range (F) | 40 F to 100 F |
| Floor Temperature Limit Range (AF Model) (F) | 40 F to 100 F |
| Floor Temperature Limit Range (AF Model) (C) | 5 C to 38 C |
| Differential Temperature (C) | ±0.5 C |
| Differential Temperature (F) | ± 1 F |
| Outdoor Temperature Display Range (F) | -58 F to 149 F |
| Outdoor Temperature Display Range (C) | -50C to 65 C |
| Temperature Display Interval (F): | +/- 1.0 F |
| Temperature Display Interval (C): | +/- 0.5 C |
| Temperature Range, Storage (C) | -30 C to 55 C |
| Temperature Range, Storage (F) | -20 F to 130 F |
| Operating Humidity Range (% RH) | 5 to 90% RH, non-condensing |
| Sensor Element | Thermistor |
| Sensors (Floor) Used | 10 kilohm NTC thermistor at 25 C (77 F) +/- 0.5F (+/-0.3C) up to 500 ft (150 M) using 18 AWG or larger wire, beta=3892. Lead Length: 10 ft. (3050 mm). |
| Floor Sensor Temperature Rating (F) | -58F to 230F |
| Floor Sensor Temperature Rating (C) | -50C to 110C |
| Electrical Connections | Wire-clamp screw terminals |
| Terminal Designations | TH, TH, Sensor, Sensor |
| Dimensions (in.) | 2.8 in wide x 4.6 in high x 1.0 in deep |
| Dimensions (mm) | 7 cm wide x 12 cm in high x 2.5 cm deep |
| Weight (kg) | 0.1 kg |
| Weight (lb) | 0.2 lb |
| Tradeline Value | Tradeline |
| Ambient Temperature Range (C) | 0 C to 70 C |
| Ambient Temperature Range (F) | 32 F to 158 F |